Skip to main content Help Control Panel

Electrical engineering and power transmission

Electrolysis Package

ECOCONTACT Package for Diaphragm Cells Chlorine/Soda

Mobile short-circuiter MDC55 connection

 

ECOCONTACT Package for Diaphragm Cells Chlorine/Soda

Optimize the power circuits contacts to gain more than 5% of energy comsumption in operation and minimize maintenance costs.
Return on investment < 6 mois
For all diaphragms cells (MDC 55, LV81, H4, …)


The usage of too aggressive tools for the pickling of the contact surfaces degrades their geometry and increases their drift in time.

Example for a cell 148 kA Voltage gain ΔU Power saved
Anode Washers 104 mV 15,3 kW
Intercells

64 mV 9,4 kW

ECOCONTACT benefits

Total power saved per cell : 25 kW
Annual total energy gain : 25 kW x 8000h= 200 000 kWh/year/cell
Estimated kWh cost = 0,06 EUR

Annual Economic Gain : 200 000 kWh x 0,06 EUR = 12 000 EUR

Cost of ECOCONTACT equipment : 5000 EUR

Return on ECOCONTACT investment : <5 months
ECOCONTACT lifetime per connexion : > 5 years

 

ECOCONTACT® Application

Chlorine/Soda Electrolysis

Jumper Switch    150 KA  MDC55 electrolysis diaphragm

Mobile short-circuiter MDC55 connection

Example of application : 150 kA mobile short-circuiter for diaphragm
cell MDC55


Measure Table

  • Room Intensity: ≈ 144 KA
  • Connexion dimension: 230 x 300mm
  • Power density: 2 A/mm²


Without ECOCONTACT


With ECOCONTACT

Thermal Gain

Y

A et B

180 °C 108°C 70°C 40%


Advantages

  • High decrease of connection temperature.
  • Compensation of planarity and pods tightening defects on the cell.
  • Preservation of the cell joint.

 