ECOCONTACT Package for Diaphragm Cells Chlorine/Soda
Optimize the power circuits contacts to gain more than 5% of energy comsumption in operation and minimize maintenance costs.
Return on investment < 6 mois
For all diaphragms cells (MDC 55, LV81, H4, …)

The usage of too aggressive tools for the pickling of the contact surfaces degrades their geometry and increases their drift in time.
| Example for a cell 148 kA | Voltage gain ΔU | Power saved | |
| Anode Washers | ![]() |
104 mV | 15,3 kW |
| Intercells |
|
64 mV | 9,4 kW |
ECOCONTACT benefits
Total power saved per cell : 25 kW
Annual total energy gain : 25 kW x 8000h= 200 000 kWh/year/cell
Estimated kWh cost = 0,06 EUR
Annual Economic Gain : 200 000 kWh x 0,06 EUR = 12 000 EUR
Cost of ECOCONTACT equipment : 5000 EUR
Return on ECOCONTACT investment : <5 months
ECOCONTACT lifetime per connexion : > 5 years