JUMPER SWITCH 120 KA

- Copper Terminals
- Trolley Jumper switch
- Large customization possible with:
- Actuators (motor, pneumatic, manual)
- Auxiliaries (limit switches, locks, control boxes)
- Adaptation to the connectiong busbars.
Main Technical Caracteristics
JUMPER SWITCH 120 KA Electrical Data
- Rated current ⇒ 120 kA
- Maximum permanent current ⇒ 140 kA
- Rated breaking capacity ⇒ 10 V / 120 kA
- Maximum breaking capacity ⇒ 20 V / 120kA
- Break speed ⇒ < 200 ms
- Useful fife of arcing contact ⇒ ~ 100 breaks / 120 kA
- Total voltage drop ⇒ ~ 0,7 V / 120 kA
- Dielectric withstand
- Between connections Jumper Sw. “OFF ⇒ 3 kV (6 kV 1 mn)
- Between frame and support ⇒ 6 kV (10 kV 1 mn)
- Total power loss at 120 kA ⇒ 85 kW
- Enclosure contacts and mechanism ⇒ IP 54
- Interface for optional polarization system
JUMPER SWITCH 120 KA Mechanical Data
- Weight ⇒ ~ 1 T.
- Force of rolling on rail ⇒ ~30 daN
- Vertical adjustment ( pneumatic ) ⇒ ± 150 mm
- Adjustment rooms A/B ⇒ ~ 500 mm
- Rotation indexing ( pneumatic; safety J.S. OFF,
and manual ) - Air and water hose supports
- Bridage screw supports
- Input air socket with dryer and lubricater
JUMPER SWITCH 120 KA Thermal Data
- Thermal power loss in cooling water ⇒ ~ 60 kW
- Rated water flow at Dq 20° C ⇒ ~ 3 m3 / h
- Mini water flow at Dq 40° C ⇒ ~ 1,5 m3 / h
- Water pressure ( rated flow ) ⇒ 2 bars