Skip to main content Help Control Panel

Electrical engineering and power transmission

Home «   Electrical Products «  

JUMPER SWITCH 120 KA

jumper switch high intensity high current

  • Copper Terminals
  • Trolley Jumper switch
  • Large customization possible with:
    • Actuators (motor, pneumatic, manual)
    • Auxiliaries (limit switches, locks, control boxes)
    • Adaptation to the connectiong busbars.


Main Technical Caracteristics

JUMPER SWITCH 120 KA Electrical Data

  • Rated current ⇒ 120 kA
  • Maximum permanent current ⇒ 140 kA
  • Rated breaking capacity ⇒ 10 V / 120 kA
  • Maximum breaking capacity ⇒ 20 V / 120kA
  • Break speed ⇒ < 200 ms
  • Useful fife of arcing contact ⇒ ~ 100 breaks / 120 kA
  • Total voltage drop ⇒ ~ 0,7 V / 120 kA
  • Dielectric withstand
    • Between connections Jumper Sw. “OFF ⇒ 3 kV (6 kV 1 mn)
    • Between frame and support ⇒ 6 kV (10 kV 1 mn)
  • Total power loss at 120 kA ⇒ 85 kW
  • Enclosure contacts and mechanism ⇒ IP 54
  • Interface for optional polarization system

 

JUMPER SWITCH 120 KA Mechanical Data

  • Weight ⇒ ~ 1 T.
  • Force of rolling on rail ⇒ ~30 daN
  • Vertical adjustment ( pneumatic ) ⇒ ± 150 mm
  • Adjustment rooms A/B ⇒ ~ 500 mm
  • Rotation indexing ( pneumatic; safety J.S. OFF,
    and manual )
  • Air and water hose supports
  • Bridage screw supports
  • Input air socket with dryer and lubricater

 

JUMPER SWITCH 120 KA Thermal Data

  • Thermal power loss in cooling water ⇒ ~ 60 kW
  • Rated water flow at Dq 20° C ⇒ ~ 3 m3 / h
  • Mini water flow at Dq 40° C ⇒ ~ 1,5 m3 / h
  • Water pressure ( rated flow ) ⇒ 2 bars

Information channels
Recent files